Chinese LABATMan
李晶,丁丹一,刘,罗锦
四川电力试验研究院,四川成都610072)
摘要:通过对阀控式铅酸蓄电池5h不离线放电测试方法及其放电终止电压值的研究,实现了一种安全、快速的变电站用蓄电池状态评估方法一—“50%放电”,同时满足DL/T724-2000标准对变电站仅有一组蓄电池的安全测试要求。
关键词:间控式铅酸蓄电池;容量测试;放电电压;数理统计与概率分析中图分类号:TM912.41
文献标识码:B
文章编号:1006-0847(2010)02-82-03
Researchon50%DoDtestingofVRLAbatteriesat
the transformer substation LI Jing,DIN Dan-yi, LIU Xi, LUO Jin
(SichuanElectrical Test andResearch Institute,Chengdu610072,China)
Abstract: Through a study on 5 hour discharge testing method of valveregulated leadacid (VRLA) bat-teries online and batteries's discharge final voltages, a safety and fast essessment method of SoC of VRLA batteries at the transformer substation, 50 % depth of discharge (DoD) , is realized, Which is satisfied with the safety testing requirements of the standard DL/T724-200 when there is only one battery pack at the transformersubstation.
Key words: VRLA; capacity testing, charge voltage; mathematical statistics and probability analysis
1引言
目前中国电力系统变电站全部使用阀控式铅酸蓄电池(VRLA),它是一种贫液式铅酸蓄电池。阀控铅酸蓄电池的状态对使用者来说是一个重要的参数,分别用荷电状态(SoC)和健康状态(SoH) 描述蓄电池的正常供电时间和预期寿命,其表征的均是容量特性。铅酸蓄电池的容量定义是:在规定放电温度、放电电流、放电终止电压的条件下获得的电量(Ah)。为了有效地掌握蓄电池的状态,一
收稿日期:2009-12-29 8201908 万方数据
直以来中国电力、邮电系统采用定期放电试验。这种为了检测电池运行期的能力所进行的定期放电,称为核对性放电,由测试结果可得到蓄电池的荷电状态和健康状态。由于电力系统110kV及以下电压等级的变电站往往仅安装了一组蓄电池,在 DL/T724-2000标准中规定蓄电池组不能退出运行(脱离直流母线)和只放出50%额定容量,其判别标准为蓄电池组端电压不得低于2V×N(N为电池只数),该条款不但未明确测试方法,其容量判据也未对应“放出容量不得低于80%额定容量(Ce)”。本文通过对阀控铅酸蓄电池5h不离线放电测试方法及其放电终止电压值的研究,实现了一种安全、快速的电池状态评估方法—“50%放电”。