变电站用蓄电池组重组后的试验及运行情况分析 www.batterychn.com
变电站用蓄电池组:组后的试验及运行情况分析
田秋松,张健毅,贾颖涛
(国网运行1000kV特高压南阳站,河南南阳473000)
摘要:新投运220V直流蓄电池组运行一年后,对部分不合格蓄电池进行了更换,本文仅对重组后试验和运行情况进行分析。
关键词:更换:蓄电池:试验现象:运行情况:分析
中图分类号:TM912.1
文献标识码:B
文章编号:1006-0847(2010)06-267-04
Ananalysisoftheexperimentalphenomenaandoperatingsituationsof
recombinedlead-acidbatteryintransformersubstation
TIAN Qiusong,ZHANG Jianyi,JIA Yingtao
(State GirdOperation 1000kV UHV NanyangTransformer Substation, Nanyang Henan 473000)
Abstract: After the 220 V direct current leadacid battery was put into operation for one year,part of leadacid cells failed in the performance requirements was changed. This paper made an attempt to analyze
the experimental phenomena and the operating situations after recombination of leadacid batteries Key words: change; leadacid battery; experimental phenomenon; operating situation; analysis
1引言
铅酸蓄电池在直流系统中是不可缺少的设备, 1000kV特高压南阳站的蓄电池组是由104只标称电压为2.25V的德国霍佩克产60PzV420型阀控式铅酸(VRLA)蓄电池组成的。220V直流电源作为特高压变电站的重要组成部分,直接关系到控制保护系统的稳定运行。
2008年10月该组蓄电池投人运行,2010年4 月进行整组核对性容量试验,按恒流放电Io=40A,终止电压为U=187.2V进行试验,试验以到达终止
收稿日期:2011-04-02 万方数据
电压时结束,所用时间t=9.5h,得到容量C=380Ah 容量未达到100%。又进行两次充/放电循环试验后,放电容量仍未达到100%,选出试验结束时单只蓄电池电压低于1.81V的共计16只,占整组(104只)的15%。考虑到220V直流电源在特高压变电站的重要性,同时仅运行1年半就有15% 的蓄电池出现此问题,须对其进行更换。更换后又对整组蓄电池进行了两次核对性充/放电循环试验,试验结果是放电容量达到100%,满足放电终止电压大于1.8V的要求(2-3]。
在更换后的充/放电循环试验中,出现了新电池终止电压较高,而浮充电压较低的现象。更换投运初期,新电池在蓄电池组中浮充运行电压较其他电池低,经过近10个月的运行后,新电池的浮充运行电压有所提高。