利用六角图对500kV自耦变压器进行
带负荷测试的原理与分析李志兴,许志华,张泽良,郁景礼(广东电网公司佛山供电局,广东佛山528000)
摘要:变压器投运后,必须带负荷校验保护的回路接线。介绍了利用六角图带负荷测试变压器保护接线的原理和分析方法,指出常见错误可能出现的原因,阐述了自耦变压器的结构和原理。通过500kV罗润变电站2号主变
压器本体更换工程校验了保护接线的正确性,同时也验证了分析方法的有效性。关键词:自耦变压器;六角图;带负荷测试;板性;相序;变比
中图分类号:TM411*3
文献标志码:A
文章编号:1673-7598(2013)12-0075-04
PrincipleandAnalysisMethodofTestwithLoadfor50okV
Autotransformer by Using HexangularVectorChart LI Zhixing,XU Zhi-hua,ZHANG Zeliang,YU Jingli
(Foshan Power Supply Bureau of Guangdong Power Grid Corporation,Foshan 528000,China)
Abstract:The wiring of protection loop must be tested after the commissioning of transfomer. This paper introduces the principle and noodonrasnoodooad ou onoposske causes of common mistakes, and expounds the structure and principle of autotransfomer. In the end, the wiring correctness of the
protection by proposed method is verified through replacing No. 2 main transformer in 500 kV Luodong substation. Key words: autotransfomer, hexangular vector chart; test with load; polarity; phase sequence; transfomation ratio
者主变电流二次回路改动后必须严格校验保护使用
0引言
带负荷测试就是在新投设备启动时对带电设备进行电流、电压、相位等电气量的测量,并对测量的电气量进行比较分析,以判断其接线、极性、相别等是否正确。带负荷测试对于电力系统中母线差动保护、主变压器(主变)差动保护、带方向的线路保护等具有十分重要的意义。在继电保护及自动装置的不正确动作中,有很大部分由具有方向性的保护接线错误引起,所以对于新投设备,必须掌握正确的带负荷测试方法,确保电网的安全稳定运行。利用六角图进行带负荷测试的目的是要排除设计、安装过程中的错误(如接错线、极性接反等),是目前判断保护回路接线正确与否最全面有效的方法。由于变压器各侧电流大小和相位均不同,以及变压器投人运行时回路产生的励磁涌流等特殊情况,变压器保护原理、接线更加复杂。为了防止接线错误,在主变投运前或
万方数据
的TA相序、极性以及回路接线,确保变压器保护的正确性"-。本文阐述了“六角图"的原理和绘制方法,介绍了如何利用六角图对主变保护各侧电流、电压相量进行分析判断,并通过实例进行验证3。
利用六角图对变压器带负荷测试的 1
分析方法
进行变压器带负荷测试时,需要知道变压器各侧电流大小、相位、有功、无功功率大小和流向等。首先利用相位表在保护屏依次测出变压器各侧三相电流的幅值和相位(基准相位一般取高侧A相TV二次电压做参考),在后台监控中获取变压器各侧的有功功率和无功功率的大小和流向。其次,根据所测得的数据绘制六角图,将六角图中画出的电流相位与有功功率、无功功率的受送情况进行分析比较,如图1 所示。
75 技术应用 JISHUYINGYONG