供热系统的高能耗分析与节能管理
梁山伟
(哈尔滨太平供热公司)
摘要:能源问题以及环境问题是当前国际和国内社会关注的共同问题,更切实关系到可
持续发展以及资源的合理利用。本文就集中供热系统中锅炉及管网运行中存在能耗偏高和运行浪费等问题进行了分析,并提出了解决高能耗建议和提高供热系统经济性能的一些实质性管理方法。
关键词:集中供热系统;高能耗;节能
中图分类号:TU833.1文献标识码:B
文章编号:1009-3230(2010)03=003203
HeatingSystemofHighEnergyConsumptionAnalysis
andEnergy-savingManagement
LIANG Shan -wei
(Harbin Taiping Heating Company,Harbin 150090)
Abstract:Energy and environmental issues is the current intemational and domestic social issues of common concem related to sustainable development and rational use of resources. This paper analyzes the central heating system, boiler and pipe network to run high in the presence and operation of a waste of energy and other issues, The paper presents recommendations to address the high energy consumption and
improve the economic performance of heating systems some of the substantive management. Key words:Central heating system; Excessive energy consumption; Energy Conservation
0前言
我国北方的集中供热逐步发展,大型热水锅炉、热力管网相继投入使用,运行管理及节能减排方面有待加强。集中供热系统普遍存在能耗偏高现象,这不但造成能源的巨大浪费,也给日益突出的环境问题增加了压力。集中供热应采取技术上可行、经济上合理以及环境和社会可承受的措施,以减少能源生产、使用等各个环节造成的损失和浪费,更加有效、合理的利用能源。
收稿日期:2010=02-10
修订稿日期:2010-02-21
作者商介:梁山伟(1976~),男,2001年毕业于哈尔滨工程
大学电子信息工程专业,1998年毕业于黑龙江工程学院工程机续专业。现工作于哈尔滨太平供热有限责任公司,从事锅炉供暖工作,职称:工程师,职务:供热部部长。
万方数据
1供热系统能耗偏高的原因分析 1.1设计过程中的不合理因素
(1)锅炉容量储备系数过高。热负荷值是供热设备容量选择的重要依据,可是在目前的采暖设计中菩遍存在着负荷估算偏高的现象。其原因主要有两点:第一,采用偏高的指标法进行估算。由于近年来气候变暖且各种保温材料的应用致使热指标下降,(以处于高寒地区的哈尔滨普通住宅为例,原供热指标为4770w/m,笔者通过近年来的实践认为应为25~55w/m)。第二,人为地加大安全裕量。虽然热负荷取值已经偏高,但基于长久以来偏于安全的思想,在设备选型时仍然按照所给范围的上限值选取,导致锅炉的储备系数过高。其实由于锅炉本身具备10%的超负荷运行能力已经具备一定的安全余量,这种做法完