2012年第7期(总第175期)
doi:10. 3969/j. issn. 1009 3230.2012.07.012
应用能源技术
300MW直接空冷凝汽器换热偏差
与冬季防冻的研究李永茂,王艳,高建强
(1.山西平朔煤研石发电有限责任公司朔州036800;2.华北电力大学保定071000)
摘要:空冷机组在冬季运行的过程中,空冷凝汽器存在换热偏差,影响整个机组运行的安全性和经济性。以山西平朔煤研石发电有限责任公司4#机300MW机组冬季运行为例,对其空冷换热器的管束壁温进行测量,得到偏差管存在的位置,分析原因并提出防护措施。
关键调:直接空冷凝汽器;管束偏差;防冻;冬季保护
中图分类号:TU831.3.1
文献标志码:B文章编号:1009-3230(2012)07-0039-04
Researchon3ooMwDirectAir-cooledCondenserHeat
ExchangeDeviationandWinterFrost
LI Yong-mao', WANC Yan’, CAO Jian-qiang
(1.Shanxi Pingshuo Gangue-fired Power Generation Co.,Ltd , Shuozhou 036800, China;
2.North China Electric Power University,Baoding 071003, China)
Abstract: In the process of air-cooled winter operating,the air-cooled steam condenser exist thermal deviation,influence on the safety and economy about the entire unit operation. Taking the 3OOMW direct air cooling power unit of Shanxi Pingshuo Gangue-fired Power Generation Co. , Ld as an example,measurement the heat exchange bundle wall tempwerature on the air-cooled steam condenser, get the position of the deviation tube, analyze the causes and proposed protective measures.
Key words: DACC; Bundle deviation; Anti freezing; Winter protection
0引言
山西平朔煤研石发电有限责任公司3#、4#机组为2×300MW的直接空冷机组。每台机组有空冷器24个,分为6列,每列4个冷却单元,其中每列第二个冷却单元为汽水逆流式,其余为汽水顺流式。空冷器散热管以接近60°角成等腰三角形(A型)结构,每个冷却单元下布置一台轴流风机。以4#机为例,空冷凝汽器的第四列为进汽列,空冷凝汽器有主凝汽器和分凝汽器两部分组
收稿日期:2012-05-11
修订日期:20120521
作者简介:李永茂(1970-)男,工程师,本科,长期从事电厂
万方数据
的生产技术管理工作。
39
成,主凝汽器多是汽水顺流式,它是空冷凝汽器的主体,可凝结75%~80%的蒸汽;分凝汽器是汽水逆流式,形成空冷凝汽器的抽真空区域,主要是为了能够顺畅地将系统内的空气和不凝结气体排出,避免运行中在空冷凝汽器内的某些部位形成死区,冬季形成冻结的情况1}。如图1所示空冷凝汽器的顺逆流(K/D)[2)结构示意。
直接空冷系统设计的气象资料
公司所处地区的气温日较差为25℃。极端最高气温为34.5℃,极端最低气温为零下29.2℃。多年平均风速为4.2m/s。根据长期的气象资料