第30卷第4期 2010年
12月
核科学与工程
Chinese Journal of Nuclear Science and Engineering
中国实验快堆380V应急交流
电力系统的可靠性分析
杨丽芳,杨红义,胡文军(中国原子能科学研究院,北京102413)
Vol.30No.4
Dec.
2010
摘要:针对中国实验快堆380V应急交流电力系统的系统设计及功能,运用经典故障树分析方法对其进行可靠性评价。定性分析得到了导致系统失效的支配性最小制集,定量计算得到系统的不可用度为
6.65E一12,以及最小割集重要度和灵敏度,从而对该系统的维修和试验提供参考。关键调:应急柴油发电机;故障树;最小割集;灵敏度及重要度
中图分类号:TL43
文献标志码:A
文章编号:0258-0918(2010)04-0314-07
system of the China experimental fast reactor
YANG Li-fang, YANG Hong-yi, HU Wen-jun(China Institute of Atomie Energy, Beijing 102413, China)
Abstract: According to the design and function of the 38o V emergency AC power supply system of the China Experimental Fast Reactor (CEFR), whose reliability analysis was completed through fault tree method. The minimal cut sets were obtained through the qualitative analysis. Unavailability which was also figured out through quantitative calculation is 6. 65E12, and the importance and sensitivity were worked out. The results will provide reference to the maintenance and test of the system.
Key words: emergency diesel generator; fault tree; minimal cut set; sensitivity and importance
中国实验快堆应急电力系统的功能是保证
中国试验快堆在正常运行工况、预计运行事件(包括厂外电源全部丧失)和事故工况期间及事故工况后,向安全系统和其他安全导则规定的安全重要物项供应电力,使它们能够足够可靠
收稿日期:2010-05-14;修回日期:2010-11-15
地执行其安全功能。
因此,应急电力系统的可靠性是保证其执行既定功能的重要特性。本文旨在应用故障树方法对CEFR的380V应急交流电力系统进行可靠性分析。在定性和定量分析的基础
作者简介:杨丽芳(1979—),女,山西原平人,硕士,主要从事概率安全分析专业方向 314