燃气技术GasTechnology doi:10.3969/j.issn.16715152.2017.04.003
高压燃气管道杂散电流干扰的评价分析口武汉天然气有限公司(430000)陈春晓李培王子敬周博昊肖嵩
摘要:本文通过全面的系统性评估杂散电流对高压燃气管道的影响,分析了高压管道受杂散电
流影响的影响固素,根据杂散电流种类,建立起分类评价体系,并对受杂散电流干扰严重的位置采用排流措施。
关键调:燃气管道杂散电流评价体系排流措施
EvaluationandAnalysisofStrayCurrentInterference
inHighPressureGasPipeline
Chen Chunxiao, Li Pei, Wang Zijing, Zhou Boyu, Xiao Song
Abstract :This paper comprehensively evaluate the effects of stray current to high-pressure gas pipeline,
The influencing factors of the influence of the stray current in the high voltage pipeline are analyzed. According to the type of stray current, establish classification and evaluation system, and the discharge measure is adopted in the position of the serious disturbance of the stray current
Keywords:gaspipestraycurrentevaluation system
discharge measure
1引言
武汉市天然气高压环线管道总长约146m。管道规格为Φ711×11,管道采用三层PE防腐与强制电流阴极保护联合防护,管道建成并投入运行8年,管道沿线周围环境已发生了很大变化,特别是近年武汉市现代化交通和能源建设的快速发展,埋地燃气管道存在与输配电系统、电气化铁路及其它电气设施交叉、接近或共用公共走廊的现象,随之而来,交/直流杂散电流干扰造成埋地管道腐蚀破坏的风险越来越大。
近年来,许多地区发生地铁杂散电流对燃气管道腐蚀的报道,我公司在对整个管道进行全线排查后检
161城市燃气2017/04总第506期万方数据
测出23处位置受杂散电流影响。建立高压燃气管道系统的评价体系,对埋地钢质管道进行杂散电流腐蚀的检测、评估,并采取排流保护措施,保障埋地燃气管道的长寿命安全运行具有重大的现实意义。
交流杂散电流于扰
2
由高压管道沿线23处测试点的交流干扰测试结果可知:
(1)所测试的23处测试点高压管道交流电压平均值和标准偏差均较低,说明受到的交流干扰较小;
(2)所测试的23处测试点高压管道受交流干扰