两机共用冷却塔节能优化研究和应用
公用工程设计 Pix Caalaies Besip
EnergySavingOptimizationResearchandApplication of OneCommon CoolingTower
forTwoUnits 赵莉,杨迎哲
(中国电力工程顾问集团西北电力设计院有限公司,西安710075)
ZHAO Li, YANG Ying-zhe
(CPECC Northwest Electrie Power Design Institute Co. Ltd, Xi an 710075,China)
【摘要】火力发电厂循环水系统来用两机共用一座自然通风冷却塔时,无法实现扩大单元制速行灵活性较差。研究通过对冷却塔配水系统速行合理分区,在中央整并内双层配水槽入口处安装特球的闸板启闭机,冷卸塔底部水池内设置隔墙,在冷却塔水池外隔增端部两例安装联络阅,以实现两台机组独立速行,提高冷却塔的利用率和返行可靠性,达到玲却塔节能运行、检修及维护灵活的日的。
[Abstract]in the circulating water system of a thermal power plant, the two unit can not realize the operation of the extended unit, and the flexibility is poor. Study on the reasonable partition ofthe cooling tower water distribution system in the central shaff with double water tank is installed at the entrance of the special gate hoist, the bottom ofthe cooling tower basin is arranged in the wall, in the cooling tower basin oute walls on both sides of the end of the installation to contact the valve, to achieve two units of independent operation, improve the operation
reliability ofthe cooling rate and the cooling tower tower,achieve energy saving operation, overhaul and maintenance offlexible purpose【关键词】循环水系统;自然通风冷塔:配水分区;闸板启闭机;联络阅
[Keywords ]circulating cooling water system; natural draft cooling tower; water distribution area; plate headstock gear; connection valve
【中图分类号】]TM621
【文献标志码】A
[DOI]10.13616/j.cnki.gcjsysj.2017.07.121 1引言
火力发电厂主机冷却系统通常采用带自然通风冷却塔的二次循环供水系统,两台机采用一座自然通风冷却塔。如何在两机共用一座冷却塔时能实现节能优化和方便、灵活地检修维护,是设计人员面临的一个课题,本文将从冷却塔内配水分区、中央竖并内闸板启闭机的设计、底部水池分隔及联络阀的
设计等方面分析如何实现冷却塔的节能优化 2空冷系统概述
河南某热电联产工程,建设规模为2x350MW超临界燃煤【作者简介】赵莉(1975-),女,陕西大人,高级工程师,从事火力
发电广取排水技术、水处理技术和空冷技术研究。万方数据
[文章编号】1007-9467(2017)07-0047-02
供热发电机组,冷却方式采用带自然通风冷却塔的湿式再宿环系统,钢炉采用燃煤直流炉,不堵死扩建条件。
该电厂循环水系统基本概况:本工程2x350MW机组采用扩大单元制循环供水系统,两台机的循环水系统包括1座 9500m的双曲线自然通风冷却塔;2条自流进水流道,4台立式循环水泵(温井式斜流泵),2台单背压凝汽器及2根循环水进水母管和2根循环水出水母管,每台机组所配2台循环水泵分别安装在各自的循环水泵站内。
本工程冷却塔配置
塔型:双曲线自然通风逆流式冷却塔:
冷却面积:9500m;填料:PVC塑料填料;
配水型号:单个竖井,管槽内外区均为压力配水,XPH型
47