第45卷第3期
2017年3月【回收与利用】
聚氯乙烯 Polyvinyl Chloride
循环冷却水系统节能优化分析及改造
吴习*,陈波2
(1.新疆中泰化学(集团)股份有限公司,新璧乌鲁木齐830009;
2.辽宁方大工程设计有限公司,辽宁芦岛125001)
【关键调】循环冷却水;管路阻抗运行效率;输送流量
Vol.45, No.3 Mar.,2017
【摘要】介绍了循环冷却水系统概况,并对循环冷却水系统能耗进行了评估,对循环冷却水系统节能优化进行了分析与改造:①改进泵的结构设计,从影响水泵能耗最根本的3大要素(管路阻抗、运行效率、输送流量)人手,提高水力效率;②优化系统的配置与运行。
【中图分类号】TQ325.3
[文献标志码]B
[文章编号】10097937(2017)03-003906
Energy-saving optimization analysis and upgrading of circulating cooling water system
WUXi',CHEN Bo
(1.Xinjiang Zhongtai Chemical (Group)Co.,Ltd., Urumqi 830009, China; 2.Liaoning Fangda Engineering Design Co.,Ltd.,Huludao 125001,China)
Key words: circulating cooling water; pipe impedance; operating efficiency; conveying flow
Abstract:The.circulating cooling water system was introduced,and theenergy consumption of the system was evaluated. The energy saving optimization of the system was analyzed and made.The designedstructure of the pump was improved in terms of three basic factors of influercing power consump-tion of the pump, i. e. pipe impedance, operation efficiency, and flowrate, in order to increase hydraulic efficiency. The configuration and operation of the system was optimized.
循环冷却水系统是工业生产企业处理工艺装置热负荷不可或缺的公用工程装置,其能源消耗可占企业总能源消耗量的10%~40%。近年来,研究发现循环冷却水系统中水泵在电能消耗方面存在较大的浪费,一方面,水泵的设计压力和实际运行压力远高于系统的正常需求;另一方面,部分循环水系统末端用户调节不合理,造成管网系统阻抗高,回水压力富裕较大[1]。正确核算循环水系统需电量、调整末端调节减小管网阻抗、充分利用回水富裕动能,对循环水电力消耗等指标的有效下降、系统能耗的有效降低有较大意义。
新疆中泰化学(集团)股份有限公司是从事化工生产的企业,前期通过换热设备运行数据收集、数据分析以及水力平衡计算、制定节能优化改造方案并组织实施等措施,对循环冷却水装置进行了节能
*【收稿日期】2016-03-21
优化改造,收到了良好的效果。
循环冷却水系统 1
1.1水泵概况
新疆中泰化学(集团)股份有限公司冷却循环水系统泵站位于以地面为基准-3.7m处,内设5 台冷却水泵,主要用于30万a离子膜烧碱、36万 VaPVC生产装置的公用工程车间、氟乙烯车间、电解车间和烧碱车间等换热设备的冷却使用,配套的 5台冷却塔型号为NH-4000,采用喷淋冷却方式,单台冷却能力6200m/h,配风机功率220kW。水泵配置参数见表1。
1.2系统运行模式及运行时间
模式A(冬季工况):3台冷却水泵+5台冷却塔+需冷却设备,则年平均运行时间:190d/a×24 h/d =4 560 h。
作者简介】吴习(1978一),女,现任新疆中泰化学阜康能源有限公司技术处副主任工程师。
39
万方数据