工程建设与设计
uction&BeripFirPhgine
医院建筑给水系统防水质污染措施浅析
AnalysisoftheSolutionofAnti-waterPollutioninHospitalWaterSupplySystem
罗颖,姜坤
(中国中元国际工程公司,北京100089)
LUOYingJIANGKun
(China IPPR Intermational Engineering Corporation, Beijing 100089,China)
防回流装置和回流污染、生活给水管材和腐蚀污象、热水系统和内源污染等方面探讨了在医院建筑给排水设计中防止水质污染的一些措施,
[AbstractlAccording to the characteristics of hospital construction, combined with some experience in the design of anti-water pollution problems in the hospital building water supply design, in this paper we explore some measures to prevent water pollution of water supply and drainage design in the hospital, from the way of water supply and secondary pollution, backflow preventer and backflow pollution, material of watersupplypipes and corrosionpollution,hot watersystem and endogenesispollution.
【关键词】医院建筑给水系统;防水质污染;二次染;圆流污染;腐蚀污染;内源污染
[Keywords] hospital water supply system; anti-water pollution; secondary pollution; backiflow pollution; corrosion pollution; endogenesis pollution
【中图分类号】TU246.1;TU991 1引言
[文献标志码】A
环境是人类赖以生存的基础,医院作为病人医疗、康复的场所,对环境有更高的要求。随着我国医学科技快速发展,医院建设已进人高峰期。医院的管理者和设计者,在医院的新建和改扩建过程中,都非常重视医院绿色环境的营造。医院建筑是适合医疗活动的房屋设备,它与一般民用建筑不同,有它独特的功能要求和卫生要求。防止水质污染、杜绝传染病的爆发流行,是医院建筑给排水设计中尤其需要重视的问题。
笔者结合工程实际经验,从供水方式与二次污染,防回流装置与回流污染,生活给水管材与腐蚀污染,热水系统与内源污染等方面探讨了在医院建筑给排水设计中防止水质污染的
【作者简介】罗颖(1981~),女,山东定陶人,工程师,从事给排水工程设计,(电子信箱)connie_1229@163.com。
196 万方数据
【文章编号】1007-9467(2013)02-0196-04 一些措施。
2供水方式与二次污染 2.1医院供水方式及特点
在医院建筑尤其是高层医院建筑中,加压给水系统是无法避免的。从水源取水,经加压后向用户供水,以解决供水水压、水量不足的问题是为二次加压供水。医院建筑二次加压供水通常有以下三种方式。
1)高位水箱供水方式:高位水箱供水应用最早,其供水可靠性高,比较节能,但供水压力受水箱设置高度限制,占用面积大,噪声扰民,二次污染严重。
2)变频供水方式:变频供水是目前比较常用的加压供水方式,其占地较小,供水水压恒定,污染相对较小。但是由于保留了水箱,二次污染依然存在,且供水的可靠性完全决定于供电的可靠性和水泵的机械可靠性。