试析高层民用建筑防排烟设施存在的问题及对策 Analysis on TallBuildings Smoke InfrastructureProblems and Countermeasures
刘海涛
(河北省邯郸市公安消防支队,河北邯郸056004)
LIUHai-tao
(Handan Fire Detachment, Handan 056004, China)
公用工程设计 Ale is Duip
【摘要】防排烟设施是高层民用建筑保障人民生命财产安全不可缺少的设施,尽管国家颁布的有关规范对防排烟设施从设计到施工验收均有相关规定,但实际工程中仍存在各种各样的问题,影响系统的运行效果,本文通过对高层民用建筑防持烟设施存在的问题进行研究,分析原固和危害,结合工程现状和相关规范,提出相应的解决对策
[Abstract]Smoke facilities are essential facilities oftall buildings forprotecting people’s lives and properties. Although the state has promulgatedstandards withrelevant provisions forsmokerelatedfacilitiesfrom designto construction and acceptance,butin actual project there are still a variety of problems which affect the system's operating results. Based on the problems research, causes and hazards analysis of high-level civil building smoke facilities, combined with the project status and related
specifications, the corresponding countermeasures were advanced.【关键词】防排烟;设施;问题;对策
[Key words ]smoke ; facilityiproblems ;countermeasures
【中图分类号】TU834
【文献标志码】A
防排烟设施是高层民用建筑保障人民生命财产安全不可缺少的设施,尽管国家颁布的有关规范对防排烟设施从设计到施工验收灼有相关规定,但实际工程中仍存在各种各样的问题,影响系统的运行效果。本文通过对高层民用建筑防排烟设施存在的问题进行研究,分析原因和危害,结合工程现状和
相关规范,提出相应的解决对策。 1存在的问题
笔者通过对多栋高层民用建筑设置的防排烟设施进行实例分析,发现很多工程的防排烟设施达不到规范要求的效果。主要间题有:
【作者简介1刘海涛(1974~),男,双北容城人,高级工程师,从事建筑工程防火审核验收和防火监备工作,(电子信箱)ab6699@126.com。
万方数据
[文章编号】1007-9467(2012)02-0091-04
1)自然排烟设施普遍存在达不到排烟目的的情况:
2)机械防烟设施送风量不足,余压值难以形成,其中部分送风口风速接近于零;
3)机械排烟设施的排烟量不足,其中一些排烟口风速接近于零:
4)防排烟风机的配电和控制不符合规范要求; 5)部分工程未按规范要求设置机械防排烟设施。
2问题分析
针对上述问题,逐一进行研究、分析原因和危害。具体如下。
2.1自然排烟设施达不到排烟目的
自然排烟是一种经济、简单、易操作、维护管理方便的排烟方式,但由于部分工程在设计、施工过程中不按规范要求进
91