母管制中继水系统水泵运行故障分析
刘涛
(大庆石化公司热电厂,黑龙江大庆163714)
摘要:分析了电厂母管制中继水系统运行中配套的水系出现不能并列运行间题,根据运行试验数据分析,确定了故障原因为并列运行的水泵实际性能不匹配,并通过车前水泵叶轮的技术措施,有效的解决了运行故障。
关键词:母管制;中继水泵;匹配;叶轮
中图分类号:TH38
文献标识码:B
文章编号:16714962(2016)04004302
43
Operationfaultanalvsis of relaywater svstemin commonheader svstem
Liu Tao
(Thermal Power Plant of Daqing Petrochemical Company, Daqing 163714, China)
Abstract: This paper analyzed the problem of water pumps being unable paralleling operation, which were equipped in operation of relay water system of common header system. Based on service test data analysis, it was determined that the fault was because the performances of pumps in paralleling operation did not match, technical measures of tuming water pump impeller were taken, and the operation fault was solved effectively.
Keywords : common header system; relay water pump; impeller
某石化公司热电厂除氧系统为2级除氧,1级除氧为低压除氧器,对锅炉补充水进行初步除氧加热同时回收低参数蒸汽;2级除氧为高压除氧器,对锅炉给水进行深度除氧同时回收各路高参数汽水。现有6台高压除氧器及6台低压除氧器,采用母管制连接,其中1"~3*低脱与4~6°低脱分布在厂房2端.间距15m。与之配套使用的7台中继水泵也对应分布在厂房2端.担负着向高压除氧器补水的重要任务]
1系统运行中存在的问题
原4~6"中继水泵自安装投产以来,难以与0° 3*中继水泵相互匹配,始终无法按照工艺设计要求并入中继水母管系统,致使1~3"低压除氧器经常处于超负荷运行状态.而4"、5"低压除氧器有效利用率文不高,造成钢炉给水热力除氧效果差,给水系统氧腐蚀严重,造成冬季大负荷期间中继水补水不足,1~3"低脱超负荷运行,除氧器溶解氧不合格的被动局面,直接威胁电厂安全生产。
2故障原因分析 2.1设备技术参数
中继水系统各其中0*~3"中继水泵与1*~3*低脱配套使用:4~7"中继水泵与4~6"低脱配套使用[2]。设备技术参数见表1。
表1中继水泵与低压除氧器设备技术参数
水蔡 0'~3* 4′~6* 7
型号 250Y150A 150Y II150 200AY II150 A
功率 kw 290 160 160
电流 39.7 17.8 19.7
电压 6 000 6 000 6 000
流量/(m"- h-") 472 180 240
为缓解低厂用蒸汽量不足的问题,将11"POY、 4"、5"低脱,5中继水泵投入运行:6"低脱投人做水箱。11"POY为4~6低脱加热源,入口门开5圈(约为全开的1/10),调整门开37%,压力0.02MPa。中继水泵1"、2"、5"运行,其余泵备用,中继水泵工作参数见表2。
表2中继水泵工作参数
中醚水 1 2' s
电流/A 31 31 14
出日压力/MPa
1.73 1.75 1.62