2014年第42卷第12期 2014Vol.42No.12
陕西电力
SHAANXIELECTRICPOWER
技术应用
Technology Application
直流偏磁对深圳电网主变压器的影响及
抑制措施的研究章彬,黄炜昭,陈潇
(深圳供电局有限公司,广东深圳518001)
摘要:直流偏磁超标会降低主变压器的运行稳定性及寿命。通过对电网结构、监测数据的分析,明确了地铁是深圳电网主变压器直流偏磁的主要来源,根据直流偏磁的成因及波形特点,对抑制措施透行了比较分析,提出了
采用电容隔直的方案,可解决深圳电网主变压器直流偏磁的间题。关键词:直流编磁;变压器;抑制
中图分类号:TM406
文献标志码:A
文章编号:1673-7598(2014)12-0069-04
Probe intoImpacts of DCMagneticBias on MainTransformer in
ShenzhenPowerGridanditsCountermeasures
ZHANGBi,HUANGWeizhao,CHEN Xi
(Shenzhen Power Supply Company Limited, Shenzhen 518001, China)
Abstract:DC magnetie bias which exceeds the standard will reduce the stability and lifetime of main transformer. Through the analysis of monitoring data and grid structure, the paper points out that the subway is the main source of the DC magnetic bias of the main transformer in Shenzhen power grid.According to the origin and waveform feature of the DC magnetic bias, the paper proposes a method to eliminate the DC magnetic bias by using capacitor coupling based on the comparative analysis on some suppression methods. Key words: DC magnetic bias; transfomer; suppression
变压器中性点出现直流。2012年7~12月期间,深圳
引言 o
直流偏磁是指在变压器励磁电流中出现了直流分量,引起变压器温度升高、噪声增加和振动加剧等问题。2011年5月11日后,深圳电网中有多台变压器中性点出现超过15A的直流,部分变电站达到了30A,超过了变压器的直流承受能力上限。研究分析认为造成深圳电网主变压器直流分量过高的主要原因是深圳地铁将运行铁轨作为回流网,铁轨出现多点接地,产生了杂散直流电流,通过大地注人临近变电站的接地网,导致中性点直接接地的主变压器(主变)直流分量超标。本文将通过数据分析,研究影响机理,并结合深圳电网实际情况,提出预防控制措施。
故障情况 1
2011年5月11日后,陆续发现深圳电网中有多台
万方数据
站主变中性点直流达到了近30A。主变噪声由68dB 增长至81.2dB,主变低压侧出现偶次谐波,35kV 侧第2组电容器出现严重过热,原因为4次谐波引起了谐振。
原因分析 2
直流偏磁产生的原因主要有2种,一是太阳磁暴的影响,二是直流输电的影响。太阳磁暴、直流单级运行及双极不平衡运行,均会在大地中形成直流电位分布,通过输电线路、接地变压器中性点、接地网以及大地形成通路,产生变压器中性点直流,从而
使变压器产生直流偏磁 2.1网络结构分析
直流分量注人电网需要电流通道,从网络结构方面分析,如图1所示,地中有直流电流流过时,一部分直流经变压器1的中性点流人,通过交流输电线路