JISHUJIAOLIUYUYINGYONG技术交流与应用
陕西省电力公司配电压器抽检现状分析及思考
焦才明1,黄国强2,李良书2
(1.陕西省电力公司.陕西西安710048;2.陕西电力科学研究院,陕西西安710054)
。摘要:介绍了陕西省电力公司配电变压暴拍检工作的现状,总结了抽检取得的成效及存在的间题。从映西省电。
力公司配电变压器抽检工作的实际出发,根据国网公司产品质量监督工作要求和决西省电力公司对抽检工作的
部署,就如何加强配变的抽检工作,提高配变的供货质量进行了认真的分析和思考。关键词:抽检;配电变压器;存在间题
中图分类号:TM421
文献标志码:B
文章编号:1673-7598(2011)11-0081-03
SampleInspectionSurveyofDistributionTransformerinShaanxi
Electric Power Company and its Thought JIAO Cai-ming',HUANG Guo-qiang, LI Liang-shu?
(1. Shaanxi Electric Power Company, Xi'an 710048, China;
2. Shaanxi Electric Power Research Institute,Xi'an 710054,China)
Abstract:The paper introduces the status of sample survey of distribution transformer in Shaanxi Electrie Power Company, summarizes the obtained effects and existing problems in recent years. Started from the reality of the sample inspection of distribution transformer in Shaanxi Electric Power Company,based on the requirements to the sample inspection of distribution transformer by State Grid Corporation and Shaanxi Electric Power Company, the paper makes an eamest analysis and thought on how to reinforce the
sample inspection of distribution transformer and improve supplying goods quality Key words: sample inspection;distribution transfomer;existing problems
1884台,按计划抽检27台,补充抽检22台,共49台,
配变抽检的基本情况
1
按照《国家电网公司供应商产品质量监督实施意见(试行)》及《供应商资质业绩核实和履约运行评价实施意见》的要求,公司全面加强集中招标采购物资的质量管控,采取监造和抽检等方式实施产品制造阶段的质量监督,提高入网产品质量,保障电网建设和运行质量。
今年以来,公司共组织完成了2批配变的抽检工作,全部采用抽样检测的方式,由物流服务中心组织到制造厂或各供电局进行取样,集中送至陕西电力科学研究院进行检测,检测项目包括空载损耗、负载损耗、短路阻抗、噪声水平、温升、油中溶解气体分析、变压器油耐压等7个方面。
第一批抽检计划对2010年“总部统一组织、网省具体实施"10~35kV第五批招标的10kV配变进行抽检。该批次招标配变中标供应商10家,采购数量
万方数据
涵盖了各供应商的每一种型号。第二批抽检计划对 2011年“总部统一组织、网省具体实施"10~35kV 第二批集中规模招标采购的配变进行抽检,共抽检配变13台,涵盖5家供应商的每一种型号。
公司组织的2批抽检共抽检配变62台,发现问题集中在空载损耗、负载损耗及变压器油等主要技术指标上。对抽检不合格产品,按照物资采购合同约定进行了相应处理,保证了交货设备质量合格。在后续的抽检工作中将继续关注配变的质量间题,对出现质量间题的供应商继续跟踪抽检,为建设坚强智能电网、实现“一强三优”现代公司目标提供坚强的物资保障。
存在问题分析及取得的成效 2
依照国网公司《变压器抽检技术导则》,物资部组织制定了《电力变压器产品质量抽检实施方案》
c