工程建设与设计
Cesuanwtiamn&DenigeFarFojne
谈临时高压消防给水系统消防泵控制
FirePumpControl inTemporaryHighPressureFireProtectionWaterSupplySystem
康凯,高崇连
(1.机械工业第一设计研究院,合肥230601;
2.信息产业电子第十一设计研究院科技工程股份有限公司,合肥230601)
KANG Kai',GAO Chong-lian?
(1.First Design & Research Institute , MI China,Hefei 230601, China;
2. TheIT Electronics Eleventh Design & Research Institute Scientific and Technological Engineering Corporation Lid.,Hefei 230601,China)【摘要】介绍了临时高压给水系统及稳高压给水系统的概念,明确了临时高压给水系统的定义,并给出了临时高压消防给水系统消火检按钮设置要求及消防水系的控制方式,供工程设计参考。
[Abstract Jintroducetheconceptoffire watersupplysystemofstablehighpressureandtemporaryhighpressurefireprotection watersupply system, clear definition offre water supply system ofstable-high pressure,and gives thefire water supply system ofstablehigh pressure
systemhydrant buttonto set the requirements and the firepump controlmode,inorderto supply the engineeringdesignreference【关键词]稳高压给水系统;临时高压消防给水系统;压力开关;流量开关;消防稳压系
[Keywords fire water supplysystem ofstable-high pressure; temporary high pressure fireprotection water supplysystem; pressure switch: flowswitch;jockeypump
【中图分类号】]TU998.13
【文献标志码】A
[DO1]10.13616/j.cnki.gcjsysj.2016.04.019
1引言
《消防给水及消火栓系统技术规范》(GB50974—2014,以下简称《消水规》)中对临时高压消防给水系统(以下简称"临高压")进行了明确的定义,《新消规》对消防水泵控制方式提出了明确要求。《火灾自动报警系统设计规范》(GB50116 2013,以下简称(火警规》)对消防水泵的控制要求也提出了相应规定。《火警规》第4.3.1条解释中提到"稳高压系统"的概念,并对消火栓按钮的设置及消火栓泵的启动方式做出了相
【作者简介】康凯(1982~),男,河南周口人,工程师,从事给水排水工程设计与研究,(电子信箱)konkay@163.com。
76 万方数据
【文章编号】1007-9467(2016)04-0076-03
关说明:《消水规》《火警规》中相关规定及要求不尽一致,另外,在《新消规》之前,相关国家规范中并未明确定义"临高压" 及“稳高压系统”的概念。
本文通过查阅相关国家及地方标准,以及相关文献、专著等,对“临高压"系统消火栓按钮的设置及消防水泵的控制进行探讨。
2临时高压消防给水系统
原《建筑设计防火规范》GB50016—2006,以下筒称《原建规》及原《高层民用建筑设计防火规范》(GB50045—95,以下简称(原高规》)仅在规范条文中提到"临高压"的概念,并未在规范术语中进行明确定义。《2009全国民用建筑工程技术