压缩机制冷量不确定度估算方法的研究王凌杰1,李竞2,芮延年3
(1.苏州经贸职业技术学院,江苏苏州215000;2.托格(上海)压缩机有限公司,上海201800;3.苏州大学,江苏苏州215000)
摘要:压端机制冷量不确定度估算一直是制冷专业研究探讨的间题之一。通过研究,基于误差传递理论,结合第二制冷制量热器法,构建了一种“压缩机制冷量不确定度估算方法”,并通过不确定度的估算实例进一步介绍了该方法的应用。该
方法的构建为制冷压综机性能试验台控制系统的设计、测量仪器仪表的选择提供了理论依据。关键调:误差传递理论;压缩机制冷量;第二制冷制法;不确定度
中图分类号:TH45
文献标志码:A
ResearchofanUncertaintyEstimationMethodforCompressorRefrigeratingCapacity WANG Ling-jie',LI Jing’, RUI Yan-nian
(1.Suzhou Institute of Trade&Commerce,Suzhou 215000, China;2.Tuoge(Shanghai) Compreseor Co, Lad.Shanghai 201800, China;3.Soochow Univer-sity ,Suzhou 215000,China)
Abstract:Uncertainty estimation for compressor refrigerating capacity has been one of the researches on major of refrigeration.Based on the theory of error propagation,combined with the method of the second refrigerant,a method of uncertainty estimation on testing compressor refrigerating capacity was introduced.The application of the method was further introduced by the example.This method aoaaasaaeedaesaksoooseaaa struments.
Key words: the theory of error propagation ; compressor refrigerating capacity; the method of the second refrigerant; uncertainty
引言 1
目前制冷压缩机性能测试普追采用第二制冷剂量热器法。第二制冷剂量热器法是利用电加热器的热量来平衡压缩机在试验工况下的制冷量,将测得的电加热量按一定方式进行修正,得到压缩机试验工况制冷量的一种方法。
然而在压缩机制冷量测试过程中,由于存在着较多不稳定因素,如测量方法的不同、仪器仪表的精度不同以及其他诸如环境偏离、环境波动或其它干扰的存在,使得被测量参数的真值具有一定的不确定性。国家标准规定,压缩机制冷量测试时,在试验工况稳定0.5h后,每隔15~20min测量1 次,连续测量4次,若测量数据满足相应的偏差
收稿日期:2013-0729
基金项目:科技部863子项目资助(项目编号2012AA063506) 10/am压细机技术
要求,则取其平均值作为试验结果,这种以有限次测量数据平均值作为试验结果的方法,会导致制冷量的测试结果可能具有较大误差。
为了提高测量精度,减小测量误差,本文拟利用误差传递理论,结合第二制冷剂量热器法估计测量中各个误差分量,研究构建一种压缩机制冷量不确定度估算方法,对试验结果作出科学的分析并将其正确地表达出来。
第二制冷剂量热器法 2
第二制冷剂量热器法测试系统流程如图1所示。量热器以一组直接蒸发盘管作为蒸发器,悬置在一个隔热压力容器(即量热器)的上部,电加热器安装在容器底部并浸没在第二制冷剂中(通常采用低压制冷剂R123),蒸发盘管不与第二制冷剂接触。测试时,制冷剂气体由压缩机流经
2013年05期(总第241期)量