46
doi:10.3969/j.issn.1009 3230.2012.11.011
应用能源技术
2012年第11期(总第179期)
风电场防雷接地系统的施工工艺分析
孙云
(大唐山东清洁能源开发有限公司,山东青岛,266061)
摘要:雷击事故在风电场中时有发生,为避免雷击事故中冲击电流对风力机的损害,风力机的防雷接地系统至关重要。文中结合大唐长清风电场一期工程采取的防雷接地系统方法,对风电场降防雷接地系统的施工工艺进行阐迹,通过对施工工艺的分析及接地电阻阻值的测量,得出风场中各风机的接地电阻介于2.95=3.69Q之间,说明采用多种降阻措施相结合的方法能有效的起到降低电阻的作用,同时电证明该风电场的防雷接地系统施工工艺是满足设计要求的。
关键词:风电场;接地电阻;防雷接地系统;降阻
中图分类号:TK89
文献标志码:B
文章编号:1009-3230(2012)11004604
TheConstructionProcessofLightningProtection Grounding
SysteminWindFarm
SUNYun
(DatangShandongCleanEnergyDevelopmentCO.,Ltd,QingDao266061,China)
Abstract: Lightning in the wind farm when the accident occurred, in order to avoid the impact of current lightning accident damage to the wind turbine, wind turbine lightning protection grounding system is essential. In this paper, Datang Changqing wind fam project to the lightning protection and eossooreooeaa system, through the construction process of analysis and mcasurement of earth resistance, derived wind field ground resistance among 2.95 to 3. 69, indicating that using a variety of resistance reduction method of combining measures can effectively play a role in reducing resistance, but also prove that the wind fam lightning protection grounding system construction process to meet design requirements.
Key words:Wind farm; Ground Resistance; Lightning Protection System; Reduce resistance
0
引言
近年来,我国风电装机容量呈现出跨越式增长,风电场的建设在全国各地遍地开花,然而,随着越多风电场的建设,暴漏出的问题日益增多,其中防雷击是风场面临的重要间题之一。
接地电阻是接地装置技术要求中最基本的技术指标,主要由土壤电阻、土壤和接地体之间的接触电阻、接地体本身的电阻及接地体引线的电阻等组成,其中主要由土壤电阻率及接地装置结构
收稿日期:20120921
修订日期:2012-1015
作者荫介:孙云(1975-),男,主要从事风电厂基建管理等
工作。
万方数据
来决定[1]。风电场建设的环境不同,降低接地电阻的方法通异,有些地方土壤的电阻率较低,简单设接地网便可达到设计要求,有些地方如山地,土壤电阻率高达数于欧姆,靠简单敷设接地网已远达不到降阻要求,需要采用多种降阻方法结合来达到降阻目的。目前,常用的降阻措施有外引接地法、人工降阻法、深井接地法、电解离子接地、爆破接地法等(2,3.4]。
大唐长清风电场一期工程位于长清区孝里镇境内,由33台单台容量为1500KW的风力机组成,总装机容量为4.95MW,场址属于山地地形,海拨高度为50=480m之间,根据所测风电场"土