28
doi:10.3969/j. issn.1009 3230.2016.06.009
应用能源技术
2016年第6期(总第222期)
220kVGIS组合电器罐体法兰连接处发热分析
李照泰,贾廷波
(日照供电公司,山东日照276826)
摘要:文中结合实际案例,对220kVGIS组合电器罐体法兰连接处发热的检测方式以及故障问题解决处理办法、处理过程中的有关注意事项等进行分析研究,以减少220kVGIS组合电器罐体法兰连接处发热对整体运行造成的不利影响,确保220kVGIS组合电器安全、稳定运行应用。
关键调:220kV;GIS;组合电器;罐体法兰;发热
中图分类号:TM56
文献标志码:B文章编号:1009-3230(2016)06-0028-03
HeatAnalysis of theFlangeConnectionofthe TankFlange
of220kVGISCombinationElectricAppliance
JIA Ting bo,LI Zhaotao
(RizhaoPowerSupplyCompany,Rizhao276826,ShandongProvince,China)
Abstract: Practical cases of 220 kV CIS combination of electrical heating tank flange connections and fault detection method problem solving approach, analysis and research process regarding precautions to reduce 220 kV GIS combination of electrical tank flange adverse effects on the overall operation of the heat caused by the combination of electrical 220 kV GIS ensure safe and stable operation of the application.
Key words: 220 kV; GIS; Combination of electrical appliances; Tank flange; Fever
0引言
后村站220kVCIS设备为组合电器设备,该组合电器为2008年投人运行,室外布置。2015 年8月3日,变电检修一班、电气试验班在对全站设备进行带电检测,通过红外精确测温发现220 kV电村I线线路侧CT(GISA相CT法兰接触面)、母线侧CT(GISC相CT法兰接触面)存在发热现象,最高温度达到94.2℃。如罐体长时间发热、负荷增大将加速连接法兰密封圈老化,易发生突发性的气室SF6气体压力迅速下降、SF6气泄漏等情况,而且法兰连接处发热引起故障问题发生后,还会因罐体瞬间感应电压或电流的出现,造
收稿日期:2016-0510
修订日期:20160521
作者简介:李照煮,山西省日照供电公司。万方数据
成线路故障而扩大故障的范围。2015年8月4 日,变电检修一班对设备发热部位加装短接排,加
装后设备恢复运行。 1检测分析方法
2015年8月3日,变电检修一班、电气试验班工作人员在对220kV后村变电站进行红外测温过程中发现,220kV电村I线线路侧CT、母线侧CT法兰接触面有发热,最高温度达到94.2℃,其它正常相最高温度约为43℃,环境温度约为 33℃。
通常情况下,GIS外壳接地多设置成一点接地或多点接地形式。其中,一点接地是以CIS外壳每个分段一端绝缘、一端一点接地方式设置,这种接地多以串联壳体之间法兰连接处绝缘和对地