交流与探讨
www.batterychn.com
110kV变电站蓄电池维护检测方法
研究与探讨
江红成",潘岑诚",江季声2,韩伟",黄梅",张振宇",俞鑫春"
(1.国网江苏南通供电公司,江苏南通226000;2.江苏省南通中学,江苏南通226000)
摘要:在分析间拉控式铅酸蓄电池的原理、特点,容量影响因素的基础上,对比了蓄电池电压检测方法和内阻检测方法,针对110kV变电站的特点,提出了蓄电池现场维护的方法,并用手持式智
能电池内阻测试仪针对不同的蓄电池进行了内阻测试验证,总结了蓄电池内阻检测判据。关键词:蓄电池;现场维护;110kV变电站;容量;电压:内阻
中图分类号:TM912.1
文献标识码:B
文章编号:1006-0847(2018)04-179-06
ResearchanddiscussiononmaintenancetestingmethodsofVRLA
batteriesfor 110kV substation
JIANG Hongcheng', PAN Cencheng', JIANG Jisheng’, HAN Wei', HUANG Mei',
ZHANG Zhenyu', YU Xinchun
(1.Jiangsu Nantong Power Supply Company of State Grid, Nantong Jiangsu 226000) 2. Nantong Middle School of Jiangsu province, Nantong Jiangsu 226000, Chinaj
Abstract: Based on analyzing the principle, characteristics and capacity factors of VRLA batteries the voltage detection method and internal resistance detection method are compared. According to the characteristics of 11o kV substations, the method of on-site maintenance of battery is put forward. The internal resistance test verification for different batteries is build by the hand-held intelligent battery resistance tester, and the test criteria of internal resistance of battery are summarized.
Keywords: VRLA battery; on-site maintenance; 11o kV substation; capacity; voltage; internal resistance
0引言
变电站直流电源系统作为继电保护装置、通信设备电源及断路器操作电源,应当满足安全、稳定、可靠运行。直流系统发生故障,将会造成保
收稿日期:2018-05-28
万方数据
护和断路器拒动,引发重大的电网事故。例如:当 2016年某330kV变电站(与某110kV变电站共址建设)外有一35kV出线电缆中间接头爆炸,站内所用交流电源失去时,直流电源未能提供应急电能,保护越级跳闸,造成事故扩大,导致330kV 和110kV主变压器着火烧损的严重事故。
在变电站直流系统中,蓄电池的稳定性和放电容量对直流系统安全运行起决定性作用。《国家电网公司变电运维管理规定第24分册站用直流电源
2018 No.4 Vo1.55179