Abstract : This article introduces the typical examples of design error, equipment defect and construction quality during the commision of boiler makeup water treatment system. By the technological analysis, it puts forward the countermeasure to solve the existing problem, provided technical references for
improvement and increasing of the following boiler makeup water treatment system debugging Keywords:water treatment; commissioning;power plant
0前言
近年来,新建超临界、超超临界火力发电机组陆续投运,对配套锅炉补给水处理系统出水水质、自动化水平的要求不断提高。而锅炉补给水处理系统基建调试过程由于设计疏漏、设备缺陷、施工质量、程控故障等问题,影响水处理系统调试进度、出水水质和程控投人,进而影响锅炉化学清洗、冲管等工程节点的实现。此外,锅炉补给水处理系统从全离子交换交换处理设备发展至超滤、反渗透、电渗析(EDI)的全膜处理工艺,新设备新工艺应用的过程也出现新的问题。本文通过总结锅炉补给水处理系统的长期现场调试经验,分析出现的典型问题,提供解决对策和改进建议。
收稿日期:2010-07-11修订日期:2010-07-25
作者简介:卢国华(1977-),男,硕士,工程师,主要从事电
厂化学系统调试、技术监管、腐蚀防护和化学仪表检验等方面的工作。
万方数据
1系统设计偏差问题
1.1反洗流量设计偏差影响程控调试
31
某锅炉补给水处理系统设计细砂过滤器与活性炭过滤器共用反洗水泵,每台过滤器反洗进水管母管相连,且过滤器反洗进水管只设有气动蝶阅。调试过程发现细砂过滤器和活性炭过滤器的反洗流量分别为200m/h和100m/h,反洗流量只能通过人工控制泵出口手动阀调节,造成细砂过滤器与活性炭过滤器程控调试出现困难,难以实现自动反洗程控功能。分析其原因是活性炭过滤器理论计算流量200m/h远大于实际反洗流量,造成反洗水泵流量难以同时匹配细砂过滤器与活性炭过滤器。调试期间处理对策是通过在过滤器进口管加装手动阀及反洗水泵加装变频器实现程控自动反洗功能。
1.2原水处理工艺影响反渗透系统调试
原水预处理设计采用混凝剂聚合铝和助凝剂聚丙烯酰胺,除盐设备采用反渗透装置。调试期