600MW锅炉过热器弯管氧化皮堵管分析
王学飞
(华能巢湖发电有限责任公司,安徽巢湖238015)
摘要:运行中的过热器氧化皮脱落,严重威胁机组运行安全,同时制约机组的负荷跟随能力。利用Fluent软件,对堵管过程进行分析,并对过热器弯头的内的压力和流动变化进行研究。
17
结果表明:氧化皮在弯管内积累厚度达到管径的35%40%左右时对流动的影响增大,继续增加容易导致爆管。提出运行中技术措施减少氧化皮的生成。
关键词:弯头;爆管;阻力;氧化皮;数值模拟
中图分类号:TK229.4文献标志码:B文章编号:1009-3230(2016)09-0017-03
AnalysisofPipeBendBlockedByScaleina6ooMWBoilerSuperheater
WANG Xue-fei
(Huaneng ChaohuPower Generation Co.,Ltd.Chaohu238015,Anhui Province,China) Abstract:In the operation of the superheater scale can come off, causing a serious threat to the safe operation of the unit, and restricted load following capability. By using CFD software Fluent, the plugging process was analyzed, the pressure and flow change of the elbow in the study of superheater. The results showed that : the influence of the thickness of the oxide scale on the flow was increased when the thickness of the scale reached 35% ~40% of the pipe the diameter, and when it continued to go up, it would be easy to make a burst. Technical measures were put forward to reduce the formation of oxide scale
Key words:Bend;Burst;Resistance;Scale;Numerical simulation
0引言
电站系统中“四管”泄露是中发生次数最多的一般是过热器管道泄露,因为其运行环境常常处在超温,烟气过度磨损等状态下。在此种状态下的管道,抗应力形变性能较差,在负荷波动过程中,过热器管道温度发生变化,导致内部的氧化皮脱落,堵塞在流动不畅的区域,导致管道流量减少,管壁超温造成恶性循环"]。
目前应对氧堵塞弯头导致的[2),过热器爆
管,主要采用减少负荷波动幅度,启动前加强冲洗,延长机组启动时间,增加正常启动的燃料消耗量,增加了厂用电率的降低。
目前的研究多为对氧化皮生成机理的分析,
收稿日期:201607-05
修订日期:20160815
作者简介:王学飞,男,工程师,从事火电厂运行优化研究。
万方数据
如贾建民等(3)对于氧化皮及其剥落物结构的研究,陈超等[4}对于对氧化皮清洗的特性的研究,龙会国等[5]对过热器弯管的失效的应力分析。研究多为机理分析,缺少对于氧化皮生成过程中弯管流动性的研究,文中对弯管氧化皮生成过程中流场进行分析,为相关研究提供参考。
事故分析 1
#2机组刚点火运行不久,锅炉四管泄漏报警装置显示异常,工作人员立即到就地检查,发现 70米平台高温过热器处有泄漏声,结合DCS给水流量和各点蒸汽和烟气温度确定锅炉过热器泄露。后逐步降负荷直至打闸停机。
停炉后检查发现高温过热器第9屏(从炉左数)14管(从外围向内圈数)、11屏3管和18屏3 管人口管段爆管。破口基本呈两种:一种爆口呈