【文章编号】1007-9467(2010)08-0085-04
工业厂房暖通空调的节能设计探讨
■张国鹏(中铁工程设计院有限公司,北京100038)
【摘要】根据工业厂房类建筑的特点,对工业厂房建筑的暖通&空调设计中存在的一些问题进行了研究和分析,并总结了一些设计经验对重工业车间、轻工业厂房或是有洁净度要求
的电子厂房的暖通空调设计,提出了优化设计方案,【关键词】工业厂房;车间;采暖;通风空调;设计问建
【中图分类号】TU831
【文献标志码】A
IndustrialPlantConstructionHVACDesignClass
Introduction ZHANGGuo-peng
(China Railway Engineering Design Institute, Beijing 100038,
China)
[Abstract]Thistype ofconstruction accordingto the characteristics ofindustrial plants, industrial plant construction in the heating & air conditioning design some problems, conducted research and analysis, and summarizes some design experience. A wide range of application of article, whether it is heavy plant, or light industrial plant or a plant cleanliness requirements of the electronic design of the guidance can be obtained from this article. The paper is of the general designer friends in the future construction of industrial building HVACclass to optimize the design aspects ofreference.[Key words]Industrial : building : heating :ventilation and air conditioning: design workshop
国家宏观调控投资政策对工业的支持,工业厂房建筑的设计量迅速增加。工业厂房建筑不同于一般的民用建筑,其设计过程多受制于工艺专业的要求。设计的同时要注意与消防、建筑物本身、结构梁柱、牛腿、节能等诸多方面的统筹兼顾。工业建筑自身的生产工艺要求,决定了其多样性的特点,在设计中应予以足够重视,做到设计有所针对。
万方数据
1负荷计算方面
公用工程设计 Publie Uilities Dere
工业厂房的采暖热负荷与空调冷负荷与一般民用建筑不同。根据《采暖通风与空气调节设计规范》(GB50019-2003),工业厂房的设计温度在12C ~21C;我们平时遇到的厂房大多数为机械加工厂房,采暖室内设计温度可以取14℃~16℃,空调室内设计温度可以取26℃~27℃。如果从室内设计温度你就断定厂房车间类建筑的冷热负荷并不大,那就错了。实际上,各类车间的负荷大小和组成千差万别。由于生产工艺的要求,有的厂房的要求新、排风量比较大,其新风负荷在总负荷重占得比例比较大。有的厂房常年进行热加工处理,厂房内部发热量比较大,而有的厂房内人员数量略多,劳动强度比较大,因而空调冷负荷中,湿负荷比较大。
2工业厂房的暖通空调设计中的冷热源选择
厂房类建筑多是布置在工业区内,通常有厂区
锅炉房提供蒸汽。当广区只有采暖用热或以采暖用热为主时,宜采用高温热水作为热媒。当厂区供热以工艺用蒸汽为主时,在不违反卫生、技术和节能要求的条件下,可采用蒸汽作为热媒。一般情况下,车间厂房类建筑是不采用电采暖的,原因很简单,工业用电价格比较高。即使是民用建筑如果没有拿到当地供电部门的特殊优惠,其运行价格也令业主难以承受。如果厂区内没有蒸汽或热水热源,某些不存在易燃危险的车间可以采用燃气辐射采暖,这也是一种比较经济的采暖方式。对于冷源的选择,也应结合厂区的实际情况,尽可能减少投资,节约能源利用。可倾向使用蒸汽热源溴化锂吸收制冷机组或使用VRV
85